Engineering design example

Commercial rooftop PV single-line diagram

An A3 drawing of the 74.8 kWp PV example, covering strings, inverters, AC distribution, grid connection and monitoring.

Design example · Representative commercial rooftop PV arrangement.

Drawing sheet

Electrical architecture and design limits

The power and monitoring architecture is shown with its design notes and project-specific design inputs.

Commercial rooftop photovoltaic single-line diagram showing eight strings, two inverters, AC protection, connected distribution boards, grid connection, site loads, monitoring, and protective earthing.
SS-CPV-SLD-001 · P06 · 25 September 2026 · Design example. Open full drawing

Drawing controls

What is defined and what remains open

Defined basis

Traceable topology

Eight strings of 17 modules, four strings per inverter, and one string connected to each MPPT circuit. Switch contacts are shown open by convention; they do not record operating state or establish safe isolation.

Conservative allocation

One string per MPPT

The example uses one string on each MPPT. The Huawei 24-202401 data sheet gives 27 A/MPPT and 20 A/input. The supplied inverter revision and permitted input arrangement must govern final allocation.

Design hold

Ratings remain project-specific

Cables, protective devices, fault duty, earthing, RCD, SPD, export control, fire access, and grid settings require verified project inputs.

Project drawing support