Technical drawing sample

Commercial rooftop PV single-line diagram

A controlled A3 drawing for the representative 74.8 kWp rooftop example. It shows the string-to-MPPT allocation, conversion equipment, AC collection, point of connection, monitoring path, and design hold points.

Representative concept - not a completed project. Not for construction, procurement, or energisation.

Drawing sheet

A reviewable electrical architecture with controlled limitations.

The complete representative power and monitoring architecture is presented together with its controlled design notes and project-specific hold points.

Representative commercial rooftop photovoltaic single-line diagram showing eight strings, two inverters, AC protection, distribution boards, grid connection, monitoring, and protective earthing.
Drawing SS-DP01-SLD-001, revision P01. Representative capability example only.

Drawing controls

What is fixed, excluded, and still required.

Defined basis

Traceable topology

Eight strings of 17 modules, four strings per inverter, and one string connected to each MPPT circuit.

Explicit exclusion

No parallel strings per MPPT

Two strings would produce 26.24 A at maximum-power current, above the representative inverter's published 26 A MPPT limit.

Design hold

Ratings remain project-specific

Cables, protective devices, fault duty, earthing, RCD, SPD, export control, fire access, and grid settings require verified project inputs.

Project drawing support

Develop a controlled drawing package from verified project data.

Available inputs should include the site layout, equipment data sheets, point of connection, existing SLD, cable routes, fault level, and applicable local requirements.